Programming expansion modules
Programming guide
A31003-K16-X001-3-7620
,
07/99
10-80
Hicom 100 E Version 2.1, Service manual
10.8.2.4 Defining the call duration
Call duration defines how long a sensor message is signalled at a destination extension.
The value entered x 5 seconds gives the call duration.
The maximum value is 255, i.e. 1275 seconds.
Example
: the call duration for messages from sensor 1 is to be set to 2 minutes, the time factor
to be entered is 24.
10.8.2.5 Defining the number of calls
The number of calls defines how often a destination extension is called for a sensor message.
Up to 255 calls are possible.
Example
: 10 calls are to be signalled at the destination extension for messages from sensor 1.
Input sequence Meaning Display
A2 6 4
Call duration for sensors
(select sensor 1–4 with "+" and "–" or
directly with "#")
Sensor no. 1: 255
B
* Change input Sensor no. 1:
C24
Enter the call duration time factor Sensor no. 1: 24
D<OK>
Confirm input Sensor no. 1: 24
E
<F8> Return to Start menu System administration
A recorded announcement device number can be deleted with the F3 key under point C.
Input sequence Meaning Display
A2 6 6
Number of calls for sensors
(select sensor 1–4 with "+" and "–" or
directly with "#")
Sensor no. 1: 255
B
* Change input Sensor no. 1:
C10
Enter number of calls Sensor no. 1: 10
D<OK>
Confirm input Sensor no. 1: 10
E
<F8> Return to Start menu System administration
Another number of calls can be entered by entering a value from 1 to 255 under point C.