Programming expansion module
A31003-K16-X001-3-7620, 07/99
Hicom 100 E Version 2.1, Service manual
10-81
Programming guide
10.8.2.6 Defining the call interval
The interval between two calls can be defined if there are several calls from a sensor message
to a destination extension.
The value entered x 10 minutes gives the call interval.
The maximum value is 255, i.e. 2550 minutes.
Example
: the call interval for messages from sensor 1 is to be set to 20 minutes.
10.8.2.7 Defining the disable time
The disable time entered for each sensor defines the period of time after which a new sensor
message is recognised and forwarded by the system.
The value entered x 10 minutes gives the disable time.
The maximum value is 255, i.e. 2550 minutes
Example
: the disable time for sensor 1 is to be set to 30 minutes.
Input sequence Meaning Display
A2 6 5
Call duration for sensors
(select sensor 1–4 with "+" and "–" or
directly with "#")
Sensor no.1: 255
B
* Change input Sensor no. 1:
C10
Enter the number of calls Sensor no.1: 10
D<OK>
Confirm input Sensor no. 1: 10
E
<F8> Return to Start menu System administration
An interval can be overridden by entering "0" under point C.
Input sequence Meaning Display
A2 6 7
Disable time for sensors
(select sensor 1–4 with "+" and "–" or
directly with "#")
Sensor no.1: 255
B
* Change input Sensor no. 1:
C3
Enter disable time factor Sensor no. 1: 3
D<OK>
Confirm input Sensor no. 1: 3
E
<F8> Return to Start menu System administration
The disable time can be deactivated by entering "0" under point C.