Communication
8.4 Ethernet
S7-200 SMART
System Manual, 09/2015, A5E03822230-AC
357
8.4
Ethernet
8.4.1
Overview
An Ethernet network is a differential (multi-point) network that can have up to 32 segments
and 1,024 nodes. Ethernet allows for data transfer at a high speed (up to 100 Mbit/s) and
long distances (Copper: Maximum approximately 1.5km; Optical: Maximum approximately
4.3km).
Possible Ethernet connections include connections for the following:
Programming devices
CPU-to-CPU GET/PUT communication
HMI displays
8.4.2
TCP/IP protocol
TCP/IP Ethernet allows an S7-200 SMART CPU to be linked to an Industrial Ethernet
network.
The Industrial Ethernet network includes the following features:
Communication based upon TCP/IP communication standards
Factory installed MAC address
Auto sensory full duplex or half duplex communications, 10 Mbits and 100 Mbits
Multiple connections:
Up to eight HMI connections
One programmer connection
Up to eight GET/PUT active connections
Up to eight GET/PUT passive connections