Technical specifications
A.2 S7-200 SMART CPUs
S7-200 SMART
System Manual, 09/2015, A5E03822230-AC
573
Table A- 14 Sensor power
Technical data
CPU ST20 DC/DC/DC
CPU SR20 AC/DC/Relay
Voltage range
20.4 to 28.8 V DC
20.4 to 28.8 V DC
Output current rating (max.) 300 mA (short circuit protected) 300 mA (short circuit protected)
Maximum ripple noise (<10
MHz)
< 1 V peak to peak < 1 V peak to peak
Isolation (CPU logic to sensor
power)
Not isolated Not isolated
A.2.1.2
Digital inputs and outputs
Table A- 15 Digital inputs
Technical data
CPU ST20 DC/DC/DC
CPU SR20 AC/DC/Relay
Number of inputs
12
12
Type SinkSource (IEC Type 1 sink, except I0.0
to I0.3, I0.6 to I0.7)
Sink/Source (IEC Type 1 sink)
Rated voltage
24 V DC at 4 mA, nominal
24 V DC at 4 mA, nominal
Continuous permissible voltage
30 V DC, max.
30 V DC, max.
Surge voltage
35 V DC for 0.5 sec
35 V DC for 0.5 sec.
Logic 1 signal (min.) I0.0 to I0.3, I0.6 to I0.7: 4 V DC at 8 mA
Other inputs: 15 V DC at 2.5 mA
15 V DC at 2.5 mA
Logic 0 signal (max.) I0.0 to I0.3, I0.6 to I0.7: 1 V DC at 1 mA
Other inputs: 5 V DC at 1 mA
5 V DC at 1 mA
Isolation (field side to logic)
500 V AC for 1 minute
500 V AC for 1 minute
Isolation groups
1
1
Filter times Individually selectable on each channel
(points I0.0 to I1.3):
μs: 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, 12.8
ms: 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, 12.8
Individually selectable on each channel
(points I0.0 to I1.3):
μs: 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, 12.8
ms: 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, 12.8
HSC clock input rates (max.)
(Logic 1 Level = 15 to 26 V DC)
4 HSC at 200 KHz for single phase
2 HSC at 100 KHz for A/B phase
4 HSC at 200 KHz for single phase
2 HSC at 100 KHz for A/B phase
Number of inputs on simultane-
ously
12 12
Cable length (max.), in meters
I0.0 to I0.3:
Shielded (only):
500 m normal (low-speed) inputs
50 m HSC (high-speed) inputs
All inputs:
Shielded: 500 m normal inputs,
50 m HSC inputs
Unshielded: 300 m normal inputs
I0.6 to I0.7:
Shielded (only): 500 m normal inputs
All other inputs:
Shielded: 500 m normal inputs
Unshielded: 300 m normal inputs

Table of Contents

Other manuals for Siemens Simatic S7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7 Series and is the answer not in the manual?

Siemens Simatic S7 Series Specifications

General IconGeneral
CPUVaries by model (e.g., S7-300, S7-400, S7-1200, S7-1500)
Communication InterfacesPROFIBUS, PROFINET, Ethernet, MPI
ProgrammingTIA Portal, STEP 7
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
I/O ModulesDigital, Analog, Specialty modules available
Operating Temperature0°C to 60°C (standard models)
MountingDIN rail mounting
Operating Voltage24V DC or 120/230V AC (varies by model)
Protection ClassIP20 (standard models)
MemoryVaries depending on the S7 model. Includes work memory (RAM) for program execution, load memory (EEPROM or Flash) for program storage, and system memory for operating system functions. Memory sizes range from kilobytes to megabytes.