Communication
8.5 PROFIBUS
S7-200 SMART
372 System Manual, 09/2015, A5E03822230-AC
Note
You can restrict communication writes to a specific range of V memory; this can affect HMI
communications. See
"Configuring system security" (Page 124) for more information.
8.5
PROFIBUS
The PROFIBUS protocol is designed for high-speed communications with distributed I/O
devices (remote I/O). A PROFIBUS system uses a bus master to poll DP I/O devices
distributed in a multi-drop fashion on an RS485 serial bus.
There are many PROFIBUS devices available from a variety of manufacturers. These
devices range from simple input or output modules to motor controllers and PLCs. A
PROFIBUS DP device is any peripheral device which processes information and sends its
output to the master. The DP device forms a passive station on the network (since it does
not have bus access rights) and can only acknowledge received messages or send
response messages to the master upon request. All PROFIBUS DP devices have the same
priority, and all network communication originates from the master.
A PROFIBUS master forms an "active station" on the network. PROFIBUS DP defines two
classes of masters. A class 1 master (normally a central programmable controller (PLC) or a
PC running special software) handles the normal communication or exchange of data with
the DP devices assigned to it. A class 2 master (usually a configuration device, such as a
laptop or programming console used for commissioning, maintenance, or diagnostics
purposes) is a special device primarily used for commissioning DP devices and for
diagnostic purposes.
PROFIBUS networks typically have one master and several DP I/O devices. (Refer to the
figure below.) The master device is configured to know what types of DP devices are
connected and at what addresses. The master initializes the network and verifies that the
DP devices on the network match the configuration. The master continuously writes output
data to the DP devices and reads input data from them.
When a PROFIBUS DP master configures a DP device successfully, it then owns that
DP device. If there is a second master device on the network, it has very limited access to
the DP devices owned by the first master.
The S7-200 SMART CPU is connected to a PROFIBUS network as a DP device with the
EM DP01 PROFIBUS DP module. The EM DP01 can be the communications partner of DP
V0/V1 masters. You can access the EM DP01 GSD file at Siemens Customer Support.

Table of Contents

Other manuals for Siemens Simatic S7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7 Series and is the answer not in the manual?

Siemens Simatic S7 Series Specifications

General IconGeneral
CPUVaries by model (e.g., S7-300, S7-400, S7-1200, S7-1500)
Communication InterfacesPROFIBUS, PROFINET, Ethernet, MPI
ProgrammingTIA Portal, STEP 7
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
I/O ModulesDigital, Analog, Specialty modules available
Operating Temperature0°C to 60°C (standard models)
MountingDIN rail mounting
Operating Voltage24V DC or 120/230V AC (varies by model)
Protection ClassIP20 (standard models)
MemoryVaries depending on the S7 model. Includes work memory (RAM) for program execution, load memory (EEPROM or Flash) for program storage, and system memory for operating system functions. Memory sizes range from kilobytes to megabytes.

Related product manuals