Table A- 96 Analog inputs
EM 2 x Analog Inputs / 1 x Analog Out-
puts (AM03)
EM 4 x Analog Inputs / 2 x Analog Outputs
(AM06)
Type Voltage or current (differential): Se-
lectable in groups of 2
Voltage or current (differential): Selectable
in groups of 2
±10 V, ±5 V, ±2.5 V, or 0 to 20 mA
±10 V, ±5 V, ±2.5 V, or 0 to 20 mA
Full scale range (data word)
Overshoot/undershoot range
(data word)
Voltage: 27,649 to 32,511 / -27,649 to -
32,512 Current: 27,649 to 32,511 / -
4,864 to 0
Voltage: 27,649 to 32,511 / -27,649 to -
32,512
Current: 27,649 to 32,511 / -4,864 to 0
Overflow/underflow (data word) Voltage: 32,512 to 32,767 / -32,513 to -
32,768 Current: 32,512 to 32,767 / -
4,865 to -32,768
Voltage: 32,512 to 32,767 / -32,513 to -
32,768
Current: 32,512 to 32,767 / -4,865 to -
Resolution Voltage mode: 12 bits + sign
Voltage mode: 12 bits + sign
Maximum withstand volt-
±35 V / ±40 mA ±35 V / ±40 mA
None, weak, medium, or strong
None, weak, medium, or strong
Isolation (field side to logic)
Accuracy (25°C / 0 to 55°C) Voltage mode: ±0.1% /±0.2% of full scale
Current mode: ±0.2% /±0.3% of full scale
Voltage mode: ±0.1% /±0.2% of full scale
Current mode: ±0.2% /±0.3% of full scale
Analog to digital conversion time
625 μs (400 Hz rejection)
625 μs (400 Hz rejection)
Common mode rejection 40 dB, DC to 60 Hz 40 dB, DC to 60 Hz
Operational signal range Signal plus common mode voltage must
be less than +12 V and greater than
Signal plus common mode voltage must be
less than +12 V and greater than -12 V
Cable length (max.), in meters
100 m twisted and shielded
100 m twisted and shielded