WARNING!
Be sure to wire Regenerative Resistors correctly. Do not connect
B1/ and B2.
Doing so may result in fire or damage to the Regenerative Resistor or
SERVOPACK.
1.
Connect the External Regenerative Resistor between the B1/ and B2 terminals
on the SERVOPACK.
Fig. 59: Connecting the External Regenerative Resistor between the B1/ and B2 termi-
nals on the SERVOPACK
2. Set Pn600 (Regenerative Resistor Capacity) and Pn603 (Regenerative Resist-
ance).
Refer to the following section for details on the settings.
Ä
Chap. 6.18 ‘Setting the Regenerative Resistor Capacity’ page 194
1. Remove the lead from between the B2 and B3 terminals on the SERVOPACK.
Fig. 60: Removing the lead from between the B2 and B3 terminals on the SERVOPACK
SERVOPACK Models
SGD7S-R70A, -R90A,
-1R6A, -2R8A, -R70F, -
R90F, -2R1F, and -2R8F
SERVOPACK Models
SGD7S-3R8A, -5R5A,
-7R6A, -120A, -180A,
-200A, and -330A
Sigma-7 Series SERVOPACKs
Wiring and Connecting SERVOPACKs
Wiring the Power Supply to the SERVOPACK > Wiring Regenerative Resistors
| | PROFINET Communications - SIEP YEUOC7P 02A Revision 0 | en | 104