Analog Monitor 2 Offset Voltage
Setting
Range
Setting Unit Default Set-
ting
When Ena-
bled
Classifica-
tion
Pn551 -10,000 to
10,000
0.1 V 0 Immediately Setup
(applies to Speed Control, Position Control and Torque Control)
Analog Monitor 1 Magnification
Setting
Range
Setting Unit Default Set-
ting
When Ena-
bled
Classifica-
tion
Pn552 -10,000 to
10,000
×0.01 100 Immediately Setup
(applies to Speed Control, Position Control and Torque Control)
Analog Monitor 2 Magnification
Setting
Range
Setting Unit Default Set-
ting
When Ena-
bled
Classifica-
tion
Pn553 -10,000 to
10,000
×0.01 100 Immediately Setup
(applies to Speed Control, Position Control and Torque Control)
Example for Setting the Item to Monitor to the Motor Speed (Pn006 = n.
00)
Example
+6 V
-6 V
-600
+6 00
+8 V
-8 V
-800
+800
+6 V
-6 V
-6000
+ 6000
When Pn552 = 100 (Setting Unit: ×0.01) When Pn552 = 1,000 (Setting Unit: ×0.01)
Analog monitor output voltage (V)
Motor speed
(min
-1
)
Note: The effective linearity range is ±8 V.
The resolution is 16 bits.
Approx. +10 V
Approx. -10 V
Analog monitor output voltage (V)
Motor speed
(min
-1
)
Fig. 330: Setting the Item to Monitor to the Motor Speed
You can manually adjust the offset and gain for the analog monitor outputs for the torque
reference monitor and motor speed monitor.
The offset is adjusted to compensate for offset in the zero point caused by output voltage
drift or noise in the monitoring system.
The gain is adjusted to match the sensitivity of the measuring system.
The offset and gain are adjusted at the factory. You normally do not need to adjust them.
An example of adjusting the output of the motor speed monitor is provided below.
Adjusting the Analog Mon-
itor Output
Sigma-7 Series SERVOPACKs
Monitoring
Monitoring Machine Operation Status and Signal Waveforms > Using the Analog Monitors