Alarm Code Alarm Name Possible Cause Confirmation Correction Reference
Pn600 (Regenerative
Resistor Capacity) is
set to a value other
than 0 (setting unit: 10
W) even though a
Regenerative Resistor
is not connected to
one of the following
SERVOPACKS:
SGD7S-R70A, -R90A,
-1R6A, -2R8A, -R70F,
-R90F, -2R1F, or
-2R8F.
Check to see if an
External Regenera-
tive Resistor is con-
nected and check
the setting of Pn600.
Connect an External
Regenerative
Resistor, or if a
Regenerative
Resistor is not
required, set Pn600
to 0.
Ä
Chap. 6.18
‘Setting the
Regenerative
Resistor
Capacity’
page 194
A Regenerative
Resistor is not con-
nected to one of the
following SERVO-
PACKs:
SGD7S-470A, -550A,
-590A, or -780A.
Check to see if an
External Regenera-
tive Resistor or a
Regenerative
Resistor Unit is con-
nected and check
the setting of Pn600
(Regenerative
Resistor Capacity).
Connect an External
Regenerative
Resistor and set
Pn600 to an appro-
priate value, or con-
nect a Regenerative
Resistor Unit and set
Pn600 to 0 (setting
unit: 10 W).
A failure occurred in
the SERVOPACK.
While the main cir-
cuit power supply is
OFF, turn the control
power supply to the
SERVOPACK OFF
and ON again. If an
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
A.320
(1320h)
Regenerative
Overload
The power supply
voltage exceeded the
specified range.
Measure the power
supply voltage.
Set the power supply
voltage within the
specified range.
The external regener-
ative resistance value
or regenerative
resistor capacity is too
small, or there has
been a continuous
regeneration state.
Check the operating
conditions or the
capacity using the
SigmaJunmaSize+
Capacity Selection
Software or other
means.
Change the regener-
ative resistance
value or capacity.
Reconsider the oper-
ating conditions
using the SigmaJun-
maSize+ Capacity
Selection Software
or other means.
*2
There was a contin-
uous regeneration
state because a nega-
tive load was continu-
ously applied.
Check the load
applied to the Servo-
motor during opera-
tion.
Reconsider the
system including the
servo, machine, and
operating conditions.
The setting of Pn600
(Regenerative
Resistor Capacity) is
smaller than the
capacity of the
External Regenerative
Resistor.
Check to see if a
Regenerative
Resistor is con-
nected and check
the setting of Pn600.
Correct the setting of
Pn600.
Ä
Chap. 6.18
‘Setting the
Regenerative
Resistor
Capacity’
page 194
Sigma-7 Series SERVOPACKs
Maintenance
Alarm Displays > Troubleshooting Alarms