Alarm Code Alarm Name Possible Cause Confirmation Correction Reference
A.890
(1890h)
Encoder Scale
Error
A failure occurred in
the linear encoder.
The linear encoder
may be faulty.
Replace the linear
encoder.
A.891
(1891h)
Encoder Module
Error
A failure occurred in
the linear encoder.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
linear encoder may
be faulty. Replace
the linear encoder.
A.8A0
(18A0h)
External
Encoder Error
Setting the origin of
the absolute linear
encoder failed
because the motor
moved.
Before you set the
origin, use the fully-
closed feedback
pulse counter to con-
firm that the motor is
not moving.
The motor must be
stopped while setting
the origin position.
Ä
Chap. 6.17
‘Setting the
Origin of the
Absolute
Encoder’
page 190
A failure occurred in
the external encoder.
Replace the external
encoder.
A.8A1
(18A1h)
External
Encoder Module
Error
A failure occurred in
the external encoder.
Replace the external
encoder.
A failure occurred in
the Serial Converter
Unit.
Replace the Serial
Converter Unit.
A.8A2
(18A2h)
External Incre-
mental Encoder
Sensor Error
A failure occurred in
the external encoder.
Replace the external
encoder.
A.8A3
(18A3h)
External Abso-
lute Encoder
Position Error
A failure occurred in
the external absolute
encoder.
The external abso-
lute encoder may be
faulty. Refer to the
encoder manufactur-
er’s instruction
manual for correc-
tions.
A.8A5
(18A5h)
External
Encoder Over-
speed
An overspeed error
was detected in the
external encoder.
Check the maximum
speed of the external
encoder.
Keep the external
encoder below its
maximum speed.
A.8A6
(18A6h)
External
Encoder Over-
heated
An overheating error
was detected in the
external encoder.
Replace the external
encoder.
A.b33
(1b33h)
Current Detec-
tion Error 3
A failure occurred in
the current detection
circuit.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
Sigma-7 Series SERVOPACKs
Maintenance
Alarm Displays > Troubleshooting Alarms
| | PROFINET Communications - SIEP YEUOC7P 02A Revision 0 | en | 615