Alarm Code Alarm Name Possible Cause Confirmation Correction Reference
A.bF0
(1bF0h)
System Alarm 0 A failure occurred in
the SERVOPACK.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
A.bF1
(1bF1h)
System Alarm 1 A failure occurred in
the SERVOPACK.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
A.bF2
(1bF2h)
System Alarm 2 A failure occurred in
the SERVOPACK.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
A.bF3
(1bF3h)
System Alarm 3 A failure occurred in
the SERVOPACK.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
A.bF4
(1bF4h)
System Alarm 4 A failure occurred in
the SERVOPACK.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
A.bF5
(1bF5h)
System Alarm 5 A failure occurred in
the SERVOPACK.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
A.bF6
(1bF6h)
System Alarm 6 A failure occurred in
the SERVOPACK.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If the
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
Sigma-7 Series SERVOPACKs
Maintenance
Alarm Displays > Troubleshooting Alarms