– This operation is the only way to reset alarms for Option Modules.
The alarms are not reset when you reset other alarms or when you
turn OFF the power supply to the SERVOPACK.
– Always remove the cause of an alarm before you reset the alarm.
Always check the following before you clear an alarm detected in an Option Module.
n The parameters must not be write prohibited.
The following table lists the tools that you can use to reset Option Module configuration
errors and the applicable tool functions.
Tool Function Reference
Digital Operator Fn014
& Σ-7-Series Digital Oper-
ator Operating Manual
(Manual No.: SIEP
S800001 33)
SigmaWin+ Setup − Reset Configura-
tion Error of Option Module
Ä
‘Operating Procedure’
page 634
Use the following procedure to reset alarms detected in Option Modules.
1.
Click the Servo Drive Button in the workspace of the Main Window of the Sig-
maWin+.
2. Select Reset Option Module Configuration Error in the Menu Dialog Box.
The Reset Option Module Configuration Error Dialog Box will be displayed.
Preparations
Applicable Tools
Operating Procedure
Sigma-7 Series SERVOPACKs
Maintenance
Alarm Displays > Resetting Alarms Detected in Option Modules