The offset does not use a parameter, so it will not change even if the
parameter settings are initialized.
Always check the following before you manually adjust the motor current detection signal
offset.
n The parameters must not be write prohibited.
The following table lists the tools that you can use to manually adjust the offset and the
applicable tool functions.
Tool Function Operating Procedure Reference
Digital Operator Fn00F
& Σ-7-Series Digital Operator Operating
Manual (document No. SIEP S800001 33)
SigmaWin+ Setup - Adjust
Offset - Adjust the
Motor Current
Detection Offset
Ä
‘Operating Procedure’ page 256
Use the following procedure to manually adjust the motor current detection signal offset.
1.
Operate the Servomotor at approximately 100 min
-1
.
2.
Click the Servo Drive Button in the workspace of the Main Window of the Sig-
maWin+.
3. Select Adjust the Motor Current Detection Signal Offsets in the Menu Dialog
Box.
ð
The Adjust the Motor Current Detection Signal Offsets Dialog Box will be dis-
played.
4. Click the Continue Button.
Fig. 195: Adjust the Motor Current Detection Signal Offsets - Caution
Preparations
Applicable Tools
Operating Procedure
Sigma-7 Series SERVOPACKs
Application Functions
Adjusting the Motor Current Detection Signal Offset > Manual Adjustment