FSTP (Forced Stop Input) Signal Allocation Reference
4 Enable drive when CN1-10 input signal is ON
(closed).
5 Enable drive when CN1-11 input signal is ON
(closed).
6 Enable drive when CN1-12 input signal is ON
(closed).
7 Set the signal to always prohibit drive (always
force the motor to stop).
8 Set the signal to always enable drive (always dis-
able forcing the motor to stop).
9 Enable drive when CN1-13 input signal is OFF
(open).
A Enable drive when CN1-7 input signal is OFF
(open).
B Enable drive when CN1-8 input signal is OFF
(open).
C Enable drive when CN1-9 input signal is OFF
(open).
D Enable drive when CN1-10 input signal is OFF
(open).
E Enable drive when CN1-11 input signal is OFF
(open).
F Enable drive when CN1-12 input signal is OFF
(open).
n.X
Reserved parameter (Do not change.)
n.X
Reserved parameter (Do not change.)
n.X
Reserved parameter (Do not change.)
Param-
eter No.
Size Name Setting
Range
Setting
Unit
Default
Setting
Appli-
cable
Motors
When
Enabled
Classifi-
cation
Refer-
ence
Pn518
*4
Safety
Module-
Related
Parameters
All
Sigma-7 Series SERVOPACKs
Parameter and Object Lists
List of Parameters > List of Parameters
| | PROFINET Communications - SIEP YEUOC7P 02A Revision 0 | en | 717