Page #1019 background imageLoading...
Page #1019 background image
Before executing this instruction, use the "SMTPcADD (Destination Group Setting)"
instruction or the programming tool software "FPWIN GR7" to configure logging/trace mail
settings.
Processing
The logging/trace mail settings of [S2] to [S4] are stored in the logging/trace setting area that
is specified by [S1].
The instruction can be executed when the mail send request relay is OFF (0: No request). As
an execution condition of the instruction, insert a program that checks the state of the mail
send request relay. The state of the mail send request relay can be read with the ETSTAT
instruction. Store the state that is read in a device such as an internal relay. An operation
error occurs if this instruction is executed when the send request relay is ON.
This instruction can be executed when the Ethernet initialization active flag (X61) is OFF. As
an execution condition of the instruction, insert a program that checks the status of the flag
(X61). If this instruction is executed when the flag (X61) is ON, the system relay SR9 (carry
flag CY) is set and the instruction is terminated without being executed.
When the instruction is completed successfully, the system relay SR9 (carry flag CY) and the
system data register SD29 (Ethernet communication error code) are cleared.
Precautions for programming
Insert the UNITSEL instruction immediately before this instruction and specify the unit (built-
in ET-LAN in the CPU unit) and the connection number.
For [S1] to [S4], specify the starting address of the device area that stores the string data
that indicates the set parameters, or a character constant. When specifying a device area for
an operand, set string data using the SSET instruction in advance. However, the ESSET
instruction cannot be used because the format is different.
The number of characters should not exceed 256.
Both upper and lower case characters can be used. "Abcd", "ABCD" and "abcd" are all
synonymous. However, the subject, the mail text, and the attachment file name are case-
sensitive.
This instruction is not available in interrupt programs.
Operand [S1] setting
Specify the starting address of the device area that stores the string data that indicates a
logging/trace number (string), or a character constant.
Setting
item
Settings
Setting
range
S1
Target LOG
number
Specify a target LOG number (0 to 15). Specify the keyword
“LOG=” at the beginning.
LOG=x
0 to 15
(Note 1) Upper and lower case characters can be used for specifying keywords.
Operand [S2] setting
Specify the starting address of the device area that stores the string data that indicates a
subject and a destination group number (string), or a character constant.
More than one destination group number can be specified simultaneously (maximum 8).
Numbers are specified with bits.
17.25 SMTPcLOG (Logging/Trace Mail Setting)
WUME-FP7CPUPGR-12 17-131

Table of Contents

Other manuals for Panasonic FP7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP7 Series and is the answer not in the manual?

Panasonic FP7 Series Specifications

General IconGeneral
BrandPanasonic
ModelFP7 Series
CategoryController
LanguageEnglish

Related product manuals