17.33 CIPMSET [CIP Message Data Setting (Merging)]
Ladder diagram
Available operation units
No operation unit.
List of operands
Operand Description
S1 Specify the starting device of send data to be added.
S2 Specify the data format of added send data or the device storing it.
D Specify the starting device of send data to be created.
Devices that can be specified (indicated by ●)
Operan
d
16-Bit device: 32 bit v Integer
Real
numbe
r
St
rin
g
Index
modifie
r
W
X
W
Y
W
R
W
L
W
S
S
D
D
T
L
D
U
M
WI
W
O
TS
C
S
TE
C
E
IX K H SF
D
F
" "
S1
S2
D
Outline of operation
This instruction is used to create data to be sent in the message communication of CIP.
If there already exists CIP message data in the storage destination, the data is added to the
existing CIP message data.
Processing
The data specified to be added by [S1] is added (merged) to the CIP message specified by
[D] according to the format specified by [S2].
S1: Specify the starting device of the data to be added.
When writing character string data, create data using the SSET instruction.
For character string data, specify data that contains character string length.
S2: Specify the format and size of the data to be added.
Specified range: 0 to 502 (000H to 1F6H)
17.33 CIPMSET [CIP Message Data Setting (Merging)]
17-162 WUME-FP7CPUPGR-12

Table of Contents

Other manuals for Panasonic FP7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP7 Series and is the answer not in the manual?

Panasonic FP7 Series Specifications

General IconGeneral
BrandPanasonic
ModelFP7 Series
CategoryController
LanguageEnglish

Related product manuals