12.8 SUMMER (Daylight Saving Time Acquisition)
■
Ladder diagram
■
List of operands
Operand Description
S1
Starting address of the device that stores clock data when daylight saving time starts (Specify the
clock data in the standard time.)
* The formats of the clock data of S1/S2 are the following four words.
Word
Sx + 0 Month
Sx + 1 Day
Sx + 2 Hours
Sx + 3 Minutes
S2
Starting address of the device that stores clock data when daylight saving time ends (Specify the
clock data in the daylight saving time.)
* The formats of the clock data of S1/S2 are the following four words.
Word
Sx + 0 Month
Sx + 1 Day
Sx + 2 Hours
Sx + 3 Minutes
S3
Time difference within the daylight saving time period (Unit: minute) Settable range: 0 to 180
(minutes)
D
* The following eight words are the formats for the enable/disable + clock data of D.
Word
D + 0 Enable/Disable
D + 1 Year
D + 2 Month
D + 3 Day
D + 4 Hours
D + 5 Minutes
D + 6 Seconds
D + 7 Day of the week