17.39 SEND (MC Protocol Master)
■
Ladder diagram
(Note 1) The above figure shows the case that S1=U100 (built-in ET-LAN in the CPU unit) and S2=U1
(connection number 1) are specified by the UNITSEL instruction.
■
Available operation units (●: Available)
Operatio
n unit
bit US SS UL SL SF DF
i ● ●
■
List of operands
Items Settings Setting range
S Starting address of the sender data area -
n Amount of sent data
1 to 960 words
1 to 7168 bits
D1
Type and upper address of the destination device of the partner unit
Higher
byte
Device type (Hexadecimal 2-digit) H0 to H8
Lower
byte
Upper address of the device (Hexadecimal 2-digit) H00 to HFF
D2 Lower address of the device for the partner unit. (Hexadecimal 4-digit) H0 to HFFFF (0 to 65535)
D3
Starting address of the device area of the master unit that stores the
execution result code (1 word)
■
Available word devices (●: Available)
Operan
d
16-Bit device:
32-Bit
device:
Integer
Real
numbe
r
St
rin
g
Index
modifie
r
W
X
W
Y
W
R
W
L
W
S
S
D
D
T
L
D
U
M
WI
W
O
TS
C
S
TE
C
E
IX K U H SF
D
F
" "
S ● ● ● ● ● ● ●
n ● ● ● ● ● ● ● ● ●
D1 ● ● ● ● ● ● ● ● ●
17.39 SEND (MC Protocol Master)