(Note 8) Can be specified only when the operation unit is a double-precision floating point real number (DF).
Outline of operation
The output value, to be stored in the device address specified by [D], is controlled based on
whether or not the input value specified by [S3] falls within the range bounded by the upper
and lower limits set in [S1] and [S2].
Output values are defined as follows:
Lower limit [S1] > Input value [S3] Lower limit [S1] → Output value [D]
Upper limit [S2] < Input value [S3] Upper limit [S2] → Output value [D]
Lower limit [S1] ≤ Input value [S3] ≤ Upper limit [S2] Input value [S3] → Output value [D]
For control by the upper limit only, the minimum value for the relevant operation unit is
specified as the lower limit [S1].
For control by the lower limit only, the maximum value for the relevant operation unit is
specified as the upper limit [S1].
Min. value
Max. value
0
US
-32768
SS
0
UL
-2147483648
SL
Negative infinite
SF
65535 32767 4294967295 2147483647
Positive infinite
Processing
Example 1) When the operation unit is 16-bit (US, SS)
Example 2) Operation unit: 32 bits (UL, SL)
10.15 LIMT (Upper and Lower Limit Control)
10-60 WUME-FP7CPUPGR-12