(a) Area in which the string to be taken out is stored (b) Area in which the string that is taken out is stored
(1) Storage area size (2) Character count
Precautions for programming
When the number of characters of [S2] is greater than the number of characters in the string
of [S1], the transferal is performed for the number of characters of [S1].
When the number of characters in [S2] is larger than the storage area size of [D], the
transferal is performed for the storage area size of [D].
When specifying with a character constant, the maximum is 256 characters.
When specifying an empty string for [S1], the result is always 0.
Flag operations
Name Description
SR7
SR8
(ER)
To be set in the case of out-of-range in indirect access (index modification).
To be set when the destination range is outside the accessible range.
To be set when [S2] (number of characters) is out of the range.
To be set when the number of characters is larger than the storage area size for [S1].
To be set when a data table with a storage area size of 0 or 65535 is specified.
SR9 (CY)
To be set when the number of characters taken out is larger than the storage area size of
[D].
14.34 ELEFT (Takeout of the Left Side of a String: With Storage Area Size)
WUME-FP7CPUPGR-12 14-135

Table of Contents

Other manuals for Panasonic FP7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP7 Series and is the answer not in the manual?

Panasonic FP7 Series Specifications

General IconGeneral
BrandPanasonic
ModelFP7 Series
CategoryController
LanguageEnglish

Related product manuals