EasyManua.ls Logo

Panasonic FP7 Series - Page 925

Panasonic FP7 Series
1222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settings
Partner unit IP address: 1111:1222::1555:0:0:1999, Partner unit port number: 10000, Unused
connection disconnect time: 30000
Examp
le 3
S2 "IPv4=192.255.100.11,PORT=2500,DISCONT=50"
Settings
Partner unit IP address: 192.255.100.11, Partner unit port number: 2500, Unused connection
disconnect time: 50
<When specifying Server (when connecting to FP7)>
The master unit port number is set by being incremented by one for each connection from
the setting start connection number to the setting end connection number. The unused
connection disconnect time is not incremented.
An error occurs if the port number exceeds 65535 when it is incremented.
Setting
item
Settings
S2
Master unit port
number
(Essential)
Specify the master unit port number (1 to 65535) of setting start
connection.
Specify the keyword "PORT=" at the beginning.
PORT=xxxx
Unused connection
disconnect time
(Essential)
Specify unused connection disconnect time (0 to 4294967295: 10 ms unit).
However, when 0 is specified, connection is not automatically
disconnected.
Specify the keyword "DISCOUNT=" at the beginning.
DISCONT=xxxx
Setting example
Examp
le 1
S2 "PORT=9000,DISCONT=0"
Settings Master unit port number: 9000, Unused connection disconnect time: 0
Examp
le 2
S2 "PORT=10000,DISCONT=30000"
Settings Master unit port number: 10000, Unused connection disconnect time: 30000
Examp
le 3
S2 "PORT=10000,DISCONT=70"
Settings Master unit port number: 10000, Unused connection disconnect time: 70
Operand [D1] setting
Specify the device address storing a setting start connection number or a constant.
Setting
item
Settings Setting range
D1
Setting start connection
number
Specify setting start connection number. 1 to 216
(maximum)
Operand [D2] setting
Specify the device address storing a setting end connection number or a constant.
17.6 CONSET (User Connection Setting)