EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 1096

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.32
SEL-400 Series Relays Instruction Manual Date Code 20171006
Reporting
Signal Profiling
SPAQgg (Analog Quantities for Signal Profiling)
Enter any analog quantity available in the relay from the Analog Quantity list in
this freeform setting.
SPAR (Signal Profile Acquisition Rate)
Although you can select as many as 20 analog quantities, the signal acquisition
rate is the same for all analog quantities. Select an acquisition rate of 1, 5, 15, 30,
or 60 minutes.
SPEN (Signal Profile Enable)
Use this SELOGIC control equation to specify conditions under which the profil-
ing must take place. If there are no conditions, be sure to set SPEN = 1, or else no
data are recorded (default value of NA disables the function).

Table of Contents

Related product manuals