EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Figure 5.39 Starter Zone Characteristic

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.59
Date Code 20171021 Instruction Manual SEL-421 Relay
Protection Functions
Out-of-Step Logic (Zero Settings)
The purpose of the starter zone is to reduce the sensitivity of the power-swing
detector by allowing the PSB elements to assert only for those trajectories of the
positive-sequence impedance (Z1) that could possibly move into the characteris-
tic of any distance element during a power swing. The area of the starter zone is a
rectangle that encompasses all the distance characteristics that must be blocked
during a power swing, as shown in Figure 5.39. Furthermore, if the out-of-step
tripping (OST) is enabled, the starter zone also encompasses the largest relay
characteristic set for the OST logic (Zone 7; see Out-of-Step Tripping (OST)—
Zero Settings Element on page 5.68). The algorithm automatically calculates the
Starter Zone from the Z2MP–Z5MP, XP2–XP5, and RP2–RP5 Group settings,
using the following equations:
R_SZ = max (2 • Z2P, OOSB2, 1.5 • Z3P, OOSB3, 1.5 • Z4P, OOSB4, 1.5 •
Z5P, OOSB5)
X_SZ = max (3 • Z2P, OOSB2, 2 • Z3P, OOSB3, 2 • Z4P, OOSB4, 2 • Z5P,
OOSB5)
The slope detector typically detects the majority of power-swing conditions.
However, there are some system conditions for which the slope detector may not
operate. To ensure correct relay power-swing operation, the OSB function also
includes two additional detectors: a swing signature detector and a dependable
PSB detector.
The Swing Signature Detector
The swing signature detector (SSD) complements the slope detector and supple-
ments the dependable PSB logic. To distinguish a power swing from a system
fault, the swing signature detector uses the combination of a step change in the
system voltage and the assertion of distance-element-based protection elements
(see Figure 5.40).
Figure 5.39 Starter Zone Characteristic
Starter Zone
j X
R

Table of Contents

Related product manuals