EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Figure 6.17 345 Kv Tapped Line Zero-Sequence Network

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.75
Date Code 20171021 Instruction Manual SEL-421 Relay
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
32V Reverse Directional Check
You set Z0MAG equal to Z
0L1
plus Z
0L2
so the fault locator provides correct
results for internal faults not located on the tap (that is, source T is extremely
weak and provides practically no infeed).
Figure 6.17 is the zero-sequence network for the 345 kV tapped overhead transmission
line.
If z0 is less than Z0F during a reverse unbalanced fault, 32V incorrectly declares
that the fault is forward with respect to the relay location (CT shown in
Figure 6.17). The relay automatically sets Z0F equal to one-half Z0MAG.
Equation 6.47 is the apparent zero-sequence impedance measured by 32V during
reverse unbalanced faults:
Equation 6.47
Equation 6.48
Use the following two assumptions to simplify the calculations:
1. Assume the power system is purely reactive
2. Ignore source impedances Z
0R
and Z
0T
(a conservative assumption)
Figure 6.17 345 kV Tapped Line Zero-Sequence Network
where:
Z
0P
= parallel combination of the Line 3 impedance, transformer
high-side reactance (neglect resistance), and the parallel com-
bination of the transformer low-side and Bus T impedance in
parallel with the transformer tertiary impedance, in parallel
with Line 2 and the Bus R impedance (see Figure 6.17).
where:
Z
0PP
= the parallel combination of the transformer low-side and Bus T
impedance in parallel with the transformer tertiary impedance
Z
0T
Z
M
Z
L
Z
H
S
Z
0L3
Z
0L2
Z
0L1
I
O
I
O
Z
0R
Z
0S
R
T
SEL-421
z
0
Z
0L1
Z
0P
+=
Z
0P
Z
0L3
jX
H
Z
0PP
++Z
0L2
Z
0R
+

=

Table of Contents

Related product manuals