Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
Calculate the effect of transformer low side and transformer tertiary impedances.
Equation 6.49
Use these assumptions to create a simplified form of the downstream parallel
impedance (from Equation 6.48).
Equation 6.50
Calculate the parallel impedance using Z
base
from Equation 6.45.
Equation 6.51
To determine whether the zero-sequence voltage-polarized 32V element always
operates correctly during reverse unbalanced faults, check the following condition:
Z0F < |Z
0L1
| + |Z
0P
|
6.44 < 6.44 + 3.8
6.44 < 10.24
The condition is satisfied; the reverse zero-sequence voltage-polarized direc-
tional element decision is correct during reverse unbalanced faults.
Pole-Open Detection
The setting EPO offers two options for deciding what conditions signify an open
pole, as listed in Table 6.19.