EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Table 6.19 Options for Enabling Pole-Open Logic

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.77
Date Code 20171021 Instruction Manual SEL-421 Relay
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
Select the second option because a 52A contact is available. The relay uses both
open-phase detection and status information from the circuit breaker to make the
most secure decision.
EPO := 52. Pole-Open Detection (52, V)
Pole-Open Time Delay on Dropout
The setting 3POD establishes the time delay on dropout after the Relay Word bit
3PO deasserts. This delay is important when you use line-side potential trans-
formers for relaying. Use the 3POD setting to stabilize the ground-distance ele-
ments in case of pole scatter during closing of the circuit breaker(s).
3POD := 0.500. Three-Pole Open Time Dropout Delay (0.000–60 cycles)
DCB Trip Scheme
This application example uses DCB trip scheme. In this scheme high-speed trip-
ping occurs during internal autotransformer faults when the communications
channel is not available.
The DCB trip scheme consists of the following three sections:
Starting elements
Coordination timers
Extension of the blocking signal
Starting Elements
You can select nondirectional elements (NSTRT), directional elements (DSTRT),
or both to detect out-of-section faults behind the local terminal. These elements
send a blocking signal to Station R to prevent unwanted tripping during out-of-
section faults. Nondirectional elements are always faster than directional ele-
ments, because directional elements need additional time to process the direc-
tional decision. Select both types of elements for this application.
Assign Relay Word bit NSTRT (Nondirectional Start) to OUT102 to start trans-
mission of the blocking signal. NSTRT asserts if Level 3 residual ground over-
current element (50G3) picks up. However, Relay Word bit STOP has priority
over Relay Word bit NSTRT. If a Z2P, Z2G, or 67G2 assert, the relay halts trans-
mission of the blocking signal that nondirectional overcurrent elements started.
Table 6.19 Options for Enabling Pole-Open Logic
Option Description
EPO := V The logic declares a single-pole open if the corresponding phase undervolt-
age element asserts and the open-phase detection logic declares the pole is
open. Select this option only if you use line-side potential transformers for
relaying purposes. A typical setting for the 27PO, pole-open undervoltage
threshold, is 60 percent of the nominal line-to-neutral voltage.
Do not select this option when shunt reactors are applied because the volt-
age slowly decays after the circuit breaker opens. With this option selected,
the relay can incorrectly declare LOP during a pole-open condition if there
is charging current that exceeds the pole-open current threshold.
EPO := 52 The logic declares a single-pole open if the corresponding 52A contact
(e.g., 52AA1) from the circuit breaker deasserts and the open-phase detec-
tion logic declares that the pole is open.

Table of Contents

Related product manuals