EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 414

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.78
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
You have enabled three levels of residual ground overcurrent elements. The
Level 2 residual ground directional overcurrent element provides communica-
tions-assisted tripping for internal unbalanced faults. The Level 3 residual ground
overcurrent element provides nondirectional start (50G3) and directional start
(67G3).
The Relay Word bit DSTRT asserts if any of the following elements pick up:
Zone 3 phase-distance elements (Z3P)
Zone 3 ground-distance elements (Z3MG)
Level 3 residual ground directional overcurrent element (67G3)
Relay Word bit DSTRT is useful when a bolted close-in three-phase fault occurs
behind the relay. If the polarizing voltage for the distance elements collapses to
zero, the corresponding Zone 3 supervisory phase-to-phase current level detec-
tors latch the Zone 3 phase-distance elements. Therefore, the Zone 3 phase-
distance characteristics do not need a reverse offset for this particular situation.
Assign Relay Word bit DSTRT (Directional Start) to OUT102 to start transmis-
sion of the blocking signal.
OUT102 := NSTRT AND NOT STOP OR DSTRT.
OUT103 stops the local transmitter from sending the blocking signal to the
remote terminal.
OUT103 := STOP OR 3PT.
Time delay on pickup prevents transmission of the blocking signal if a transient
causes a reverse-looking element to pick up momentarily. Set the corresponding
timer to 1 cycle.
Z3XPU := 1.000. Zone 3 Reverse Pickup Time Delay (0.000–16000 cycles)
You can also extend the blocking signal during current reversals. Set the corre-
sponding dropout timer to 5 cycles.
Z3XD := 5.000. Zone 3 Reverse Dropout Delay (0.000–16000 cycles)
Coordination Timers
The forward-looking elements that provide high-speed tripping at Station S must
be delayed momentarily so the local circuit breaker does not trip for external
faults behind Station R. This time delay provides time for the nondirectional and
reverse-looking blocking elements at Station R to send a signal to Station S
during out-of-section faults. This particular time delay is the coordination time
for the DCB trip scheme. There are separate coordination timers for Zone 2 dis-
tance elements (21SD) and Level 2 residual directional overcurrent elements
(67SD).
The recommended setting for the 21SD timer is the sum of the following three
times:
Control input recognition time (including debounce timer)
Remote Zone 3 distance protection maximum operating time
Maximum communications channel time
If the control input time delay on pickup debounce timer is zero, the maximum
recognition time for the control input is 0.125 cycles. Assume a remote Zone 3
distance protection pickup time of one cycle; the remote Zone 3 distance protec-
tion should operate faster than the local Zone 2 distance protection because the

Table of Contents

Related product manuals