EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Figure 6.24 Nonhomogeneous Angle Setting

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.99
Date Code 20171021 Instruction Manual SEL-421 Relay
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Nonhomogeneous Correction Angle
TANGG, the nonhomogeneous angle setting, also helps prevent overreach or
underreach for ground faults at a specific fault location by compensating the
angle of the reactance line.
Set TANGG to prevent the Zone 1 quadrilateral ground-distance reactance mea-
surement from overreaching for ground faults located at the remote bus. Use the
result from Equation 6.60 (T2 in Quadrilateral Ground Polarizing Quantity on
page 6.29).
TANGG := —2.2. Nonhomogeneous Correction Angle (–40.0 to +40.0 degrees)
Zero-Sequence Current Compensation Factors
Zero-sequence current compensation helps keep the phase and ground-distance
elements at the same reach if you set the phase reach and the ground reach equal
per zone (e.g., Z1MP = XG1). Ground-distance elements should measure fault
impedance in terms of positive-sequence impedance only.
The relay has three zero-sequence current compensation factors (k01, k0, and
k0R). The Zone 1 ground-distance element has a dedicated zero-sequence current
compensation factor (k01). Advanced Settings are enabled for this particular
example (EADVS := Y), so you must set two additional independent zero-
sequence current compensation factors, one for forward-looking zones (k0) and
one for reverse-looking zones (k0R).
The zero-sequence cable impedance depends on the return path of the ground
fault current during ground faults. The zero-sequence current compensation fac-
tors must be set so the Zone 1 ground-distance elements do not see ground faults
external to the protected cable, while Zone 2 and Zone 3 ground-distance ele-
ments must see all internal ground faults.
The SEL-421 uses Equation 6.61 to calculate the A-Phase-to-ground distance
reactance measurement.
Equation 6.61
Figure 6.24 Nonhomogeneous Angle Setting
X
R
TANGG > 0
TANGG = 0
TANGG < 0
XAG
Im V
A
I
POL
e
j TANGG

*

Im z1 I
A
k01 3I
0
+I
POL
e
j TANGG

*
• • 
------------------------------------------------------------------------------------------------------------------------------=

Table of Contents

Related product manuals