EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Figure 6.25 External Ground Fault

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.102
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
k0M := 6.105. Forward Zones ZSC Factor Magnitude (0.000–10)
k0A := 44.5. Forward Zones ZSC Factor Angle (–180.0 to +180.0 degrees)
k0MR := 6.105. Reverse Zones ZSC Factor Magnitude (0.000–10)
k0AR := 44.5. Reverse Zones ZSC Factor Angle (–180.0 to +180.0 degrees)
Distance Element Common Time Delay
Set the operation time delay of both the phase and ground-distance elements.
Zone 1
There is no need to delay Zone 1 distance protection; the relay trips instanta-
neously for faults in Zone 1.
Z1D = 0.000. Zone 1 Time Delay (OFF, 0.000–16000 cycles)
Zone 2
Zone 2 distance protection must coordinate with downstream Zone 1 distance
protection plus the downstream circuit breaker operating time and a safety mar-
gin. A typical Zone 2 phase and ground-distance time delay setting is 20 cycles.
Z2D := 20.000. Zone 2 Time Delay (OFF, 0.000–16000 cycles)
Short Adjacent Lines
You do not need to consider the following fault current return path scenario for
this application example; this information is provided here for applications with
short adjacent lines. Figure 6.25 illustrates an important consideration if you
apply time-delayed Zone 2 ground-distance protection to backup downstream
Zone 1 ground-distance protection.
Fault current flows through the sheath and ground with respect to the cable
because the sheath is grounded at each end during external ground faults. How-
ever, because you must make sure that Zone 2 ground-distance elements see all
ground faults at remote Station R, the k0 setting was for the ground path only.
Therefore, Zone 2 ground-distance protection may overreach for external ground
faults, especially for the case of a short adjacent line. The solution is to increase
Zone 2 time delay.
Figure 6.25 External Ground Fault
SEL-421
Conductor
I
F
I
C
I
S
I
G
Sheath
Ground
RS
Zone 2 Ground Distance
Zone 1 Ground Distance

Table of Contents

Related product manuals