3.23
Date Code 20171021 Instruction Manual SEL-421 Relay
Testing
Technical Support
Step 7. Apply the sources to confirm operation of MBC2.
a. Apply the source test current by slowly increasing the magnitude
of I
B
.
b. Observe the
RELAY ELEMENT LCD screen.
Relay Word bit MBC2 asserts when |I
B
| 2.5 A, indicating that
the relay impedance calculation is less than the Z2MP reach
setting.
Technical Support
We appreciate your interest in SEL products and services. If you have questions
or comments, please contact us at: