EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Figure 6.21 Quadrilateral Ground-Distance Element Reactive Reach Setting

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.95
Date Code 20171021 Instruction Manual SEL-421 Relay
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Employ each zone of distance protection as follows:
Zone 1—Instantaneous underreaching direct tripping
Zone 2—Forward-looking tripping elements for the POTT scheme
and backup tripping
Zone 3—Current reversal guard for the POTT scheme, echo tripping,
and weak infeed logic
Zone 1 Reactance
The reach of the Zone 1 reactance measurement of the quadrilateral ground-dis-
tance elements must meet the same requirement as that for Zone 1 mho phase-
distance protection; the reach setting can be no greater than 80 percent of the
cable.
XG1 = 0.8 • |Z
1L1
| = 0.8 • 0.48 = 0.38
XG1 := 0.38. Zone 1 Reactance (OFF, 0.05–64 secondary)
Zone 1 Resistance
Find RG1 (Zone 1 Resistance) from the per-unit reach m of the Zone 1 reactance.
Use Equation 6.55, which is Equation 3 in Appendix A—Quadrilateral Reactive
Reach Versus Resistive Reach Setting Guideline from the paper Digital Commu-
nications for Power System Protection: Security, Availability, and Speed (go to
selinc.com for a copy of this paper):
Equation 6.55
XG1 is set at 80 percent of the underground cable (i.e., m = 0.8 per-unit); the pos-
itive-sequence reactance of the cable, X
1L1
, is 0.323 secondary (from the rect-
angular form of Z
1L1
in Table 6 .2 3).
Figure 6.21 Quadrilateral Ground-Distance Element Reactive Reach Setting
X
XG
R
where:
m = per-unit reach of XG1
R = RG1 (the Zone 1 resistance)
X
1L1
= positive-sequence transmission line reactance
m1
R
X
1L1
20
-------------------------=

Table of Contents

Related product manuals