EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 430

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.94
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Set Zone 1 phase-distance protection to 80 percent of the cable positive-sequence
impedance.
Z1MP = 0.8 • Z
1L1
= 0.8 • 0.48 = 0.38
Z1MP := 0.38. Zone 1 Reach (OFF, 0.05–64 secondary)
Zone 2 Phase-Distance Element Reach
Zone 2 phase-distance protection must have adequate reach to detect all phase-to-
phase, phase-to-phase-to-ground, and three-phase faults along the protected
cable. Set Zone 2 phase-distance protection to 120 percent of the cable positive-
sequence impedance. With this reach, high-speed tripping occurs via the commu-
nications channel for faults located in the last 20 percent of the cable.
Z2MP = 1.2 • Z
1L1
= 1.2 • 0.48 = 0.58
Z2MP := 0.58. Zone 2 Reach (OFF, 0.05–64 secondary)
Zone 3 Phase-Distance Element Reach
Zone 3 phase-distance protection must have adequate reach to prevent unwanted
tripping during current reversals when the parallel line is in service because this
example uses a POTT scheme. So that Zone 3 has greater fault coverage than
Zone 2 at the remote terminal, set the reach to remote Zone 2 and rely upon the
length of the protected cable as the safety margin.
Z3MP = Z2P = 0.58
Z3MP := 0.58. Zone 3 Reach (OFF, 0.05–64 secondary)
Ground-Distance Elements (21XG)
Quadrilateral Ground-Distance Element Reach
The main advantage of ground-distance protection is that Zone 1 provides instan-
taneous protection independent of the communications channel. Typically cable
faults have little fault resistance; it is advantageous to conservatively set the resis-
tance reach for quadrilateral ground-distance protection. Supplement quadrilat-
eral ground-distance protection with directional negative-sequence overcurrent
elements. The directional negative-sequence overcurrent elements employed in
the communications-assisted tripping scheme provide excellent resistive cover-
age for high-resistance ground faults (e.g., a contaminated pothead flashes over).
The reactive reach for each zone of quadrilateral ground-distance protection lies
on the relay characteristic angle (Z1ANG), rather than on the ordinate (reactance)
of the impedance plane (see Figure 6.21).

Table of Contents

Related product manuals