Date Code 20171021 Instruction Manual SEL-421 Relay
Protection Functions
Inverse-Time Overcurrent Elements
Inverse-Time Overcurrent Elements
The SEL-421 provides three selectable operating quantity inverse-time overcur-
rent elements. Ten different time-overcurrent characteristics (5 U.S. and 5 IEC
curves) are available.
Each time-overcurrent element can be configured to operate on the line current
(i.e., IW terminal current or the sum of the IW and IX terminal currents) depend-
ing upon setting LINEI; or circuit breaker operating quantities, with the terminal
source depending upon settings BK1I and BK2I.
Symmetrical component current quantities are available only for the line-current
source. Tab le 5.61 defines the available setting choices for operating quantities
and the corresponding analog quantity name as found in Section 12: Analog
Quantities.