EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Figure 5.120 Synchronism-Check Settings

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.160
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Functions
Synchronism Check
Setting E25BK
n
:= Y2
If E25BKn is set to Y2, where n = 1 or 2, the synchronizing logic verifies that
both the reference and synchronizing voltages are healthy and that the difference
between them is less than the 25VDIF setting before enabling the synchronism-
check logic. It combines the logic that is used when E25BKn is set to Y or Y1.
Synchronism-Check Settings Example
This example uses a two-circuit breaker arrangement (see Figure 5.119). Set the
synchronism-check enable settings:
E25BK1 := Y. Synchronism Check for Circuit Breaker BK1 (Y, N, Y1, Y2)
E25BK2 := Y. Synchronism Check for Circuit Breaker BK2 (Y, N, Y1, Y2)
NOTE: If Global setting NUMBK = 1,
the synchronism-check logic is not
executed for Breaker 2.
If you are using the relay on a single circuit breaker, enable synchronism check
for only one circuit breaker (E25BK1 := Y and E25BK2 := N).
Figure 5.120 shows the correspondence between the synchronism-check settings
and the two-circuit breaker application example. All of these settings are listed in
Section 10: Settings. The following subsections explain these settings and include
an explanation of Alternative Synchronism-Check Voltage Source 2 settings (see
Figure 5.131).
Synchronism-Check Logic Outputs
Figure 5.121 shows the correspondence between synchronism-check logic out-
puts (Relay Word bits) and the two-circuit breaker arrangement. These Relay
Word bits assert to logical 1 (e.g., 59VP equals logical 1) if true and deassert to
logical 0 (e.g., 59VS1 equals logical 0) if false. Table 5.81 lists these Relay Word
bits.
Figure 5.120 Synchronism-Check Settings
Bus 2
Bus 1
Line
BK2
BK1
Synchronism-Check Voltage Source 1
SYNCS1 — designate voltage input
KS1M — adjust magnitude to reference
KS1A — adjust angle to reference
Synchronism-Check Voltage Reference
SYNCP — designate voltage input
25VL — voltage window/low threshold
25VH — voltage window/high threshold
Synchronism-Check Across Breaker BK2
25SFBK2 — max. slip frequency
ANG1BK2 — max. angle difference 1
ANG2BK2 — max. angle difference 2
TCLSBK2 — breaker close time
BSYNBK2 — block synch check (SEL
OGIC)
Synchronism-Check Across Breaker BK1
25SFBK1 — max. slip frequency
ANG1BK1 — max. angle difference 1
ANG2BK1 — max. angle difference 2
TCLSBK1 — breaker close time
BSYNBK1 — block synch check (SEL
OGIC)
Synchronism-Check Voltage Source 2
SYNCS2 — designate voltage input
KS2M — adjust magnitude to reference
KS2A — adjust angle to reference
1
3
1
. . .
. . .
. . .

Table of Contents

Related product manuals