EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Figure 6.5 Quadrilateral Ground-Distance Element Reactive Reach Setting

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.28
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
Zone 1 Reactance
Zone 1 quadrilateral ground-distance reactance reach must meet the same
requirement as that for Zone 1 mho phase-distance protection; the reach setting
should be no greater than 80 percent of the line.
XG1 = 0.8 • Z
1L1
= 3.18
XG1 := 3.18. Zone 1 Reactance (OFF, 0.05–64 secondary)
Zone 1 Resistance
Find RG1 (Zone1 resistance) from the per-unit reach m of the Zone 1 reactance.
Use Equation 6.9, which is Equation 3 in Appendix A—Quadrilateral Reactive
Reach Versus Resistive Reach Setting Guideline from the paper Digital Commu-
nications for Power System Protection: Security, Availability, and Speed. You can
find a copy of this paper on the SEL website at selinc.com.
Equation 6.9
XG1 is set at 80 percent of the transmission line (i.e., m = 0.8 per-unit); the posi-
tive-sequence reactance of the overhead transmission line X
1L1
is 3.977 sec-
ondary (from the rectangular form of Z
1L1
in Table 6 .8 ).
Equation 6.10
Figure 6.5 Quadrilateral Ground-Distance Element Reactive Reach Setting
X
XG
R
where:
m = per-unit reach of XG1
R = RG1, the Zone 1 resistance
X
1L1
= positive-sequence transmission line reactance
m1
R
X
1L1
• 20
------------------------=
Z
1L1
3.98 87.6=
R
1L1
jX
1L1
+=
0.167 j3.977+=

Table of Contents

Related product manuals