EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 363

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.27
Date Code 20171021 Instruction Manual SEL-421 Relay
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
Ground-Distance Elements (21MG and 21XG)
Mho Ground-Distance Element Reach
Employ each zone of distance protection as follows:
Zone 1—Instantaneous underreaching direct tripping
Zone 2—Forward-looking tripping elements for the POTT scheme
and backup tripping
Zone 3—Current reversal guard for the POTT scheme, echo tripping,
and weak infeed logic
Zone 1 Mho Ground-Distance Element Reach
Zone 1 mho ground-distance reach must meet the same requirement as that for
Zone 1 mho phase-distance protection; the reach setting should be no greater than
80 percent of the line.
Z1MG = 0.8 • Z
1L1
= 3.18
Z1MG := 3.18. Zone 1 (OFF, 0.05–64 secondary)
Zone 2 Mho Ground-Distance Element Reach
Zone 2 mho and ground-distance reach must meet the same requirement as that
for Zone 2 mho phase-distance protection; the reach setting is 120 percent of the
line.
Z2MG = 1.2 • Z1L1 = 4.78
Z2MG := 4.78. Zone 2 (OFF, 0.05–64 secondary)
Zone 3 Mho Ground-Distance Element Reach
Zone 3 mho ground-distance reach must meet the same requirement as that for
Zone 3 mho phase-distance protection; it equals the Zone 2 reach.
Z3MG = Z2MG = 4.78
Z3MG := 4.78. Zone 3 (OFF, 0.05–64 secondary)
Quadrilateral Ground-Distance Element Reach
The reactive reach for each zone of quadrilateral ground-distance protection lies
on the relay characteristic angle (Z1ANG), rather than on the ordinate (reactance)
of the impedance plane (see Figure 6.5).

Table of Contents

Related product manuals