EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Table 10.19 Synchrophasor Order in Data Stream (Voltages and Currents)

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.31
Date Code 20171021 Instruction Manual SEL-421 Relay
Communications Interfaces
Synchrophasors
Table 10.19 Synchrophasor Order in Data Stream (Voltages and Currents)
Synchrophasors
a
(Analog Quantity Names)
a
Synchrophasors are included in the order shown (i.e., voltages, if selected, will always precede
currents).
Included When Global Settings
Are as Follows:
Polar
b
b
Polar coordinate values are sent when PHFMT := P.
Rectangular
c
c
Rectangular (real and imaginary) values are sent when PHFMT := R.
Magnitude Angle Real Imaginary
V1mPMM
d
d
Where:
m
= Y if PHVOLT includes Y
m
= Z if PHVOLT includes Z.
V1mPMA V1mPMR V1mPMI PHDATAV := V1 or ALL
VA mPMM VAmPMA VAmPMR VAmPMI
VBmPMM VBmPMA VBmPMR VBmPMI PHDATAV := PH or ALL
VCmPMM VCmPMA VCmPMR VCmPMI
I1nPMM
e
e
Where:
n
= W if PHCURR includes W
n
= X if PHCURR includes X
n
= S if PHCURR includes S.
I1nPMA I1nPMR I1nPMI PHDATAI := I1 or ALL
IAnPMM IAnPMA IAnPMR IAnPMI
IBnPMM IBnPMA IBnPMR IBnPMI PHDATAI := PH or ALL
ICnPMM ICnPMA ICnPMR ICnPMI

Table of Contents