8.39
Date Code 20171021 Instruction Manual SEL-421 Relay
Settings
DNP3 Settings—Custom Maps
DNP3 Settings—Custom Maps
The SEL-421 DNP3 custom map settings operate as described in the DNP3 Set-
tings—Custom Maps on page 12.15 in the SEL-400 Series Relays Instruction
Manual. See Table 10.14 on page 10.16 to see the default map configuration.
Bay Settings
Table 8.85 Bay Settings (Sheet 1 of 2)
Setting Prompt Default Value
MIMIC Busbar One-Line Screen Number (1–999) 9
BAYNAME Bay Name (20 characters) BAY 1
BAYLABy
a
Bay Label y
a
(max 35 pixels, 5–9 characters) LABEL y
a
EPOLDIS Enable Single-Pole Discrepancy Logic (Y, N) Y
BUSNAMy
a
Busbar y
a
Name (max 40 pixels, 6–10 characters) BUSNAM y
a
ByHMINM Breaker y
a
HMI Name (max 17 pixels, 3–4 characters) BKy
a
BzCTLNM
b
Breaker z
b
Cntl. Scr. Name (max 15 characters) Breaker z
b
52yCLSM
a
Breaker y
a
Close Status (SELOGIC Equation) 52ACLy
a
523CLSM = NA
52y_ALM
a
Breaker y
a
Alarm Status (SELOGIC Equation) 52AALy
a
523_ALM = NA
DrHMIN
c
Disconnect m HMI Name (max 17 pixels, 3–4 characters)
d
SW[m]
DrCTLN
c
Disconnect m Control Scr. Name (max 15 char.)
d
BB [m]
89AMr
c
Disconnect m N/O Contact (SELOGIC Equation)
d
1
89BMr
c
Disconnect m N/C Contact (SELOGIC Equation)
d
0
89ALPr
c
Disconnect m Alarm Pickup Delay (1–99999 cyc)
d
300
89CCNr
c
Dis. m Remote Close Control (SELOGIC Equation)
d
89CCr
89OCNr
c
Dis. m Remote Open Control (SELOGIC Equation)
d
89OCr
89CSTr
c
Dis. m Close Seal-in Time (OFF, 1–99999 cyc)
d
280
89CITr
c
Dis. m Close Immobility Time (OFF, 1–99999 cyc)
d
20
89CRSr
c
Disconnect m Close Reset (SELOGIC Equation)
d
89CLr OR 89CSIr
89CBLr
c
Disconnect m Close Block (SELOGIC Equation)
d
NA
89OSTr
c
Dis. m Open Seal-in Time (OFF, 1–99999 cyc)
d
280
89OITr
c
Dis. m Open Immobility Time (OFF, 1–99999 cyc)
d
20
89ORSr
c
Disconnect m Open Reset (SELOGIC Equation)
d
89OPNr OR 89OSIr
89OBLr
c
Disconnect m Open Block (SELOGIC Equation)
d
NA
89CIRr
c
Dis. m Close Immob. Time Reset (SELOGIC Equation)
d
NOT 89OPNr
89OIRr
c
Dis. m Open Immob. Time Reset (SELOGIC Equation)
d
NOT 89CLr
MDELEn
e
Analog Quantity <Blank>
MDNAMn
e
Pretext <Blank>
MDSETn
e
Text Formatting {w.d} <Blank>
MDCLRn
e
Post-Text