14.21
Date Code 20171006 Instruction Manual SEL-400 Series Relays
ASCII Command Reference
Command Description
CSU TERSE
The TERSE command option returns an event summary report in Compressed
ASCII format without labels; the relay sends only the data (including header data).
You can apply the TERSE option with any of the CSU commands except CSU
ACK and CSU MB.
DATE
Use the DATE command to view and set the relay date. The relay can overwrite
the date that you enter by using other time sources, such as IRIG and DNP3.
Enter the DATE command with a date to set the internal clock date. You can sep-
arate the month, day, and year parameters with spaces, commas, slashes, colons,
and semicolons.
Set the year in two-digit form (for dates 2000–2099) or four-digit form. If you
enter the year as 12, the relay date is 2012. You must enter the data in the format
specified in the Global setting DATE_F.
If an IRIG-B time synchronization signal is connected to the relay, the DAT com-
mand cannot alter the month or day portion of the date. If the IRIG-B time source
is IEEE C37.118 compliant and Global setting IRIGC = C37.118, or if an Simple
Network Time Protocol (SNTP) time source is connected, the DAT command
cannot alter any time setting.
DNAME X
The DNA X command produces the ASCII names of all relay digital I/O (input/
output) quantities reported in a Fast Meter message in Compressed ASCII format.
Ta b l e 1 4.49 CSU T E R S E Co m m a n d
Command Description Access Level
CSU TERSE Return the event summary report without the label lines
in Compressed ASCII format.
1, B, P, A, O, 2
CSU n
a
TERSE
a
Parameter
n
indicates event number or serial order.
Return a particular n event summary report without the
label lines in Compressed ASCII format.
1, B, P, A, O, 2
CSU N TERSE View the oldest unacknowledged event summary without
the label lines in Compressed ASCII format.
1, B, P, A, O, 2
Table 14.50 DATE Command
Command Description Access Level
DATE Display the internal clock date. 1, B, P, A, O, 2
DATE date
a
a
Enter date parameters in the same order as Global setting DATE_F.
Set the internal clock date. 1, B, P, A, O, 2
Table 14.51 DNA Command
Command Description Access Level
DNA X Display ASCII names of all relay digital I/O. 0, 1, B, P, A, O, 2

Table of Contents