EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 1401

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17.51
Date Code 20171006 Instruction Manual SEL-400 Series Relays
IEC 61850 Communication
ACSI Conformance Statements
M7–11 conf-revision Y
M8 Unbuffered report control Y
M8–1 sequence-number Y
M8–2 report-time-stamp Y
M8–3 reason-for-inclusion Y
M8–4 data-set-name Y
M8–5 data-reference Y
M8–6 BufTim Y
M8–7 IntgPd Y
M8–8 GI Y
M8–9 conf-revision Y
Logging
M9 Log control
M9–1 IntgPd
M10 Log
M11 Control Y
M17 File transfer Y
M18 Application association
M19 GOOSE control block Y
M20 Sampled Value control block
If GSE (B31/32) Is Supported
M12 GOOSE Y
M13 GSSE Deprecated in
Edition 2
If SVC (B41/42) Is Supported
M14 Multicast SVC
M15 Unicast SVC
For All IEDs
M16 Time Y Time source with
required accuracy
shall be available.
Only the time master
is an SNTP (Mode 4
response) time
server.
All other client/
server devices
require SNTP (Mode
3 request) clients.
a
Y = supported
N or blank = not supported
Table 17.28 ACSI Models Conformance Statement (Sheet 2 of 2)
Client/Subscriber
a
Server/Publisher
a
Value/Comments

Table of Contents