EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 334

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.174
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Functions
Synchronism Check
For any case [(a), (b), (c), or (d)] in Figure 5.130, the location of V'
S1
is the loca-
tion of V
S1
a period later (this period is setting TCLSBK1, Circuit Breaker BK1
Close Time). Consider, for example, issuing a close command to Circuit Breaker
BK1. If case (b) in Figure 5.130 represents the time at which the close command
occurs, then V
S1
is the normalized synchronism-check voltage source position at
the instant the close is issued and V'
S1
is the position of V
S1
when Circuit
Breaker BK1 actually closes.
Slip Frequency
If the slip frequency exceeds setting 25SFBK1, synchronism check cannot pro-
ceed via element output 25A1BK1. Synchronism check stops because element
output 25A1BK1 deasserts to logical 0 for an out-of-range slip frequency condi-
tion, regardless of other synchronism-check conditions such as healthy voltage
magnitudes.
Synchronism check remains possible (although not necessarily advantageous) if
you use element output 25W1BK1 and the slip frequency exceeds setting
25SFBK1. Synchronism-check element 25W1BK1 does not measure slip. In this
instance, synchronism check occurs (25W1BK1 is logical 1) when the phase
angle difference between reference V
P
and V
S1
is less than angle setting
ANG1BK1.
Synchronism-Check Element Output Effects
A contradiction seems to result from analysis of case (a) in Figure 5.130; it
appears that element output 25A1BK1 should assert to logical 1 because V'
S1
is
within angle setting ANG1BK1. Note in this case, however, that V'
S1
is
approaching synchronism-check reference VP. This is where element output
25A1BK1 behaves differently than element output 25W1BK1, for setting
25SFBK1 set to some value other than OFF. As V'
S1
approaches V
P
, 25A1BK1
remains deasserted (equals logical 0) until the phase angle difference between
reference V
P
and V'
S1
equals zero degrees.
At this zero degrees difference between V
P
and V'
S1
point, element output
25A1BK1 asserts to logical 1. We know the systems will truly be in synchronism
(0 degrees between reference V
P
and V
S1
) a period later (this period is setting
TCLSBK1, Circuit Breaker BK1 Close Time). Thus, if a close command occurs
right at the instant that element output 25A1BK1 asserts to logical 1, then there
will be a zero degree phase angle difference across Circuit Breaker BK1 when
Circuit Breaker BK1 actually closes. Closing Circuit Breaker BK1 at a phase
angle difference of 0 degrees between reference V
P
and V'
S1
minimizes system
shock when you bring two asynchronous systems together.
Element output 25A1BK1 remains asserted to logical 1 as V'
S1
moves away from
reference V
P
. When the phase angle difference between reference V
P
and V'
S1
is
again greater than angle setting ANG1BK1, element output 25A1BK1 deasserts
to logical 0.
Alternative Synchronism-Check Source 2 Settings
You can program alternative input sources for the synchronism-check function in
the SEL-421. Alternative inputs give you additional flexibility to synchronize
other portions of your power system.
The SEL
OGIC control equation ALTS2 determines when the relay uses alternate
Synchronism-Check Voltage Source 2 in place of regular Synchronism-Check
Voltage Source 2. When ALTS2 is logical 1, the relay substitutes alternative Syn-

Table of Contents

Related product manuals