EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 340

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.4
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Applications Examples
230 kV Overhead Distribution Line Example
Breaker Monitor
Circuit Breaker Configuration
Set the relay to indicate that Circuit Breaker 1 is a three-pole trip circuit breaker.
BK1TYP := 3. Breaker 1 Trip Type (Single-Pole = 1, Three-Pole = 3)
Circuit Breaker 1 Inputs
The SEL-421 uses a normally open auxiliary contact from the circuit breaker to
determine whether the circuit breaker is open or closed.
52AA1 := IN101. A-Phase N/O Contact Input -BK1 (SELOGIC Equation)
Group Settings
Line Configuration
The SEL-421 has four transformer turns ratio settings that convert the secondary
potentials and currents that the relay measures to the corresponding primary val-
ues. These settings are the potential transformer and current transformer ratios
PTRY, PTRZ, CTRW, and CTRX.
Use the Y potential input for line relaying and the Z potential input for synchro-
nism check. Use the W current input for line relaying. The settings VNOMY and
VNOMZ specify the nominal secondary line-to-line voltage of the potential
transformers (see Figure 6.2).
CTRW := 100. Current Transformer Ratio—Input W (1–50000)
PTRY := 2000. Potential Transformer Ratio—Input Y (1–10000)
VNOMY := 115. PT Nominal Voltage (L-L)—Input Y (60–300 V secondary)
PTRZ := 2000. Potential Transformer Ratio—Input Z (1–10000)
VNOMZ := 115. PT Nominal Voltage (L-L)—Input Z (60–300 V secondary)
Enter the secondary value of the positive-sequence impedance of the protected
line. See Ta b l e 6 .2 for the secondary line impedances.
Z1MAG := 1.95. Positive-Sequence Line Impedance Magnitude
(0.05–255 secondary)
Z1ANG := 84.00. Positive-Sequence Line Impedance Angle (5.00–90 degrees)
Enter the secondary value of the zero-sequence impedance of the protected line.
Z0MAG := 6.20. Zero-Sequence Line Impedance Magnitude
(0.05–255 secondary)
Z0ANG := 81.50. Zero-Sequence Line Impedance Angle (5.00–90 degrees)
Enable the fault locator.
EFLOC := Y. Fault Location (Y, N)
The LL setting is the line length. This value has no defined unit; you can set the
line length in miles, kilometers, ohms, etc. For this example, set the length in
miles.
LL := 50. Line Length (0.10–999)

Table of Contents

Related product manuals