EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 428

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.92
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
You can select a common time delay or an independent time delay per zone for
phase and ground-distance protection. If you choose independent timing, evolv-
ing faults (such as those changing from single phase to multiphase) cause the
timer to reset and result in additional delay. Select common time delay for this
application.
ECDTD := Y. Distance Element Common Time Delay (Y, N)
The SOTF (switch-onto-fault) protection logic permits tripping by specified pro-
tection elements for a settable time after the circuit breaker closes.
ESOTF := Y. Switch-Onto-Fault (Y, N)
Do not enable the out-of-step logic for this application example.
EOOS := N. Out-of-Step (Y, N)
Do not enable the load-encroachment logic; the minimum apparent load imped-
ance is outside the mho phase-distance characteristics.
ELOAD := N. Load Encroachment (Y, N)
Use Level 1 high-set instantaneous phase overcurrent element for SOTF protec-
tion.
E50P := 1. Phase Instantaneous/Definite-Time Overcurrent Elements (N, 1–4)
This application does not require residual ground overcurrent protection.
E50G := N. Residual Ground Instantaneous/Definite-Time Overcurrent Ele-
ments (N, 1–4)
Enable three levels of negative-sequence overcurrent protection. Use these nega-
tive-sequence current level detectors in conjunction with the communications-
assisted tripping scheme.
E50Q := 3. Negative-Sequence Instantaneous/Definite-Time Overcurrent Ele-
ments (N, 1–4)
Use inverse-time overcurrent protection to provide backup protection for high-
resistance ground faults. The 51S1 element provides backup protection for unbal-
anced faults if both the communications-assisted and step distance protection fail
to operate.
E51S := 1. Selectable Operating Quantity Inverse-Time Overcurrent Element
(N, 1–3)
The relay automatically calculates all of the ground directional elements settings
when you select AUTO or AUTO2.
E32 := AUTO2. Directional Control (Y, AUTO, AUTO2)
Use the POTT trip scheme to quickly clear faults internal to the protected line.
ECOMM := POTT. Communications-Assisted Tripping (N, DCB, POTT,
POTT2, POTT3, DCUB1, DCUB2)
Fuses or molded case circuit breakers often protect potential transformers. Oper-
ation of one or more fuses, or molded case circuit breakers, results in a loss of
polarizing potential inputs to the relay. Loss of one or more phase voltages pre-
vents the relay from properly determining fault distance or direction.

Table of Contents

Related product manuals