EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 464

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.128
SEL-421 Relay Instruction Manual Date Code 20171021
Protection Applications Examples
Out-of-Step Logic Application Examples
You can increase the adaptive UBOSBD timer calculation in multiples of setting
UBOSBF. If UBOSBF is a multiplier of one, the relay calculates the expected
time to traverse across the inner blinders based on the rate at which the swing
moved from Zone 7 to Zone 6. Similarly, if UBOSBF is a multiplier of four, the
relay multiplies UBOSBD by four.
Out-of-Step Unblocking During Unbalanced Faults
The SEL-421 treats Zone 1 phase and ground-distance elements differently than
phase-distance elements of other zones.
Operation of either of two negative-sequence directional elements, 67QUBF (for-
ward-looking), or 67QUBR (reverse-looking), defeats the OSB logic and
unblocks the phase-distance elements (except the Zone 1 elements) when an
unbalanced fault occurs following a power swing. Therefore, the phase-distance
protection operates in the POTT scheme and high-speed clears the unbalanced
fault if it is an internal one. The time-delayed elements of associated zones also
start timing to initiate backup protection functions. The 67QUBF element
unblocks forward-looking zones and 67QUBR unblocks reverse-looking zones.
The relay supervises the 67QUBF and 67QUBR elements with negative-
sequence pickup setting 50QUBP. When you set the 50QUBP pickup level to
other than OFF, the level of negative-sequence current exceeds the 50QUBP set-
ting threshold, and the relay has made a valid directional decision (32 elements),
the relay asserts either the 67QUBF or the 67QUBR directional element after
time delay setting UBD. In this manner the relay removes out-of-step blocking
for phase-distance elements other than Zone 1 elements during unbalanced faults.
The 50QUBP setting is an advanced setting and must be coordinated with the dis-
tance protection for the protected line. Setting UBD is also an advanced setting;
set the UBD timer to coordinate clearing times with protection external to the
protected line.
For out-of-step unblocking on unbalanced faults you must do the following:
Step 1. Set EADVS := Y to enable advanced settings.
Step 2. Set the negative sequence unblocking element pickup with setting
50QUBP (Negative-Sequence Current Supervision).
Coordinate with line distance protection.
Step 3. Set the unblock delay timer UBD (Negative-Sequence Current
Unblock Delay).
Coordinate clearing times with other protection.
If a power swing center is on the line under protection, the Zone 1 distance ele-
ments at one or both terminals may operate if the OSB is removed. For example,
during an unstable swing, if an external A-Phase ground fault occurs beyond the
remote terminal R in Figure 6.28, the A-Phase ground-distance elements at both
terminals operate correctly; that is, A-Phase distance element picks up in Zone 2
at the S terminal, and in reverse Zone 3 at the R terminal. However, all Zone 1
phase and ground-distance elements at both terminals may also operate if the
swing center is within the Zone 1 reach and a negative-sequence overcurrent ele-
ment removes the OSB. The undesirable operations of Zone 1 elements may trip
all three phases at both terminals for an external A-Phase fault.
The SEL-421 uses a directional negative-sequence element (67Q1T) to supervise
the out-of-step blocking of Zone 1 distance elements. 67Q1T is independent from
67QUBF and 67QUBR, which are used to defeat the OSB for distance elements
other than Zone 1 elements. This separation gives you a choice to control the
Zone 1 element operations during an unstable swing situation.

Table of Contents

Related product manuals