SEL-421 Relay Instruction Manual Date Code 20171021
Protection Applications Examples
Autoreclose and Synchronism-Check Example
In this application example, the relay does not perform a synchronism check on
single-pole reclosing.
Synchronism-Check Solution
Apply the synchronism-check function as follows for Circuit Breaker 2:
Use the A-Phase voltages from the line and Bus 2 for the
synchronism check across Circuit Breaker 2.
Select the high voltage magnitude and low voltage magnitude
thresholds for the synchronism check.
Select the maximum voltage angle difference allowed for both
reclosing and manual closing.
Select conditions that block the synchronism check.
Synchronism-Check Relay Settings
Select the relay settings for this application example.
Relay Configuration
Enable synchronism check for Circuit Breaker 2 only.
E25BK1 := N. Synchronism Check for Breaker 1 (Y, N, Y1, Y2)
E25BK2 := Y. Synchronism Check for Breaker 2 (Y, N, Y1, Y2)
Synchronism-Check Element Reference
Select A-Phase voltage from the line source for the synchronism check reference.
VAY is the reference for the synchronism check because this analog input is con-
nected to the line potential.
SYNCP := VAY. S y n c h R e f e r e n c e ( VAY, V B Y, V C Y, VA Z , V B Z , V C Z )
Set the low-voltage threshold that supervises synchronism check equal to 60 V
secondary.
25VL := 60.0. Voltage Window Low Threshold (20.0–200 V secondary)
Set the high-voltage threshold that supervises synchronism check equal to 70 V
secondary.
25VH := 70.0. Voltage Window High Threshold (20.0–200 V secondary)
Circuit Breaker 2 Synchronism Check
Select A-Phase voltage from Bus 2 for the synchronism check source. VBZ is the
source for the synchronism check because this is the bus potential.
SYNCS2 := VBZ. Synch Source 2 (VAY, VBY, VCY, VAZ, VBZ, VCZ)
Both the line reference and bus source voltages are measured line-to-neutral. Set
the ratio factor equal to unity.
KS2M : = 1.00. Synch Source 2 Ratio Factor (0.000–30)