A.5
Date Code 20171021 Instruction Manual SEL-421 Relay
Firmware, ICD File, and Manual Versions
Firmware
Added Isolated IP mode (NETMODE = ISOLATEIP) which permits
IEC 61850 GOOSE messages on two ports but restricts IP traffic to just
one port.
Added pulsed remote bits in Automation SELOGIC.
Added FRQST and PMLEGCY settings to maintain backward settings
compatibility.
Added aliasing capability for the phasors, analogs, and digitals in the
synchrophasor data.
Enhanced the report time records to save the active UTC offset
(UTCOFF) value with each report. Now, when the relay collects a
report, it assigns the time stamp based on the UTC time and the
UTCOFF value at the time the relay stores the report.
Removed the port uniqueness requirements for the PMOUDP1 and
PMOUDP2 settings.
Enhanced the embedded HTTP server user interface to be consistent
with other SEL relays.
Improved the Sequential Events Recorder (SER) resolution to 0.5 ms for
level sensitive contact inputs.
Modified the relay to support MMS file transfer service even if the relay
contains an invalid CID file.
Modified the embedded HTTP server web access to always require a
valid relay Access Level 1 (ACC) password.
Updated the maximum and minimum line metering data (MET M com-
mands) to display local time for all data.
Reset the port timeout on transmitted Telnet messages.
Updated the profile and compressed profile commands (PRO and
CPRO, respectively) to display the available analog signal profiling
records regardless of the state of the signal profile enable (SPEN) set-
ting.
Changed the result of a SELOGIC control equation math error from NAN
(not a number) to the previously stored valid result.
Improved Port 5 functionality to disable auto-messages when the auto-
messages setting is equal to no (AUTO=N).
Changed the IEC 61850 Configured IED Description (CID) file to sup-
port non-Relay Word bit binary elements included in a GOOSE mes-
sage.
Improved dual breaker applications by allowing different CT ratios for
all functions.
Modified the relay to continue to send synchrophasors data after a
change in port settings.
Changed the Global Setting Message Format (MFRMT) so that when it
is set to Fast Message (FM), the freeform settings PMAQ, PMAA,
PMDG, and PMDA are hidden.
Changed the Station ID label in the COMTRADE configuration (.cfg)
file to prevent non-alphanumeric characters per the IEEE C37.111-1999
COMTRADE standard.
Modified the firmware to prevent IP traffic from becoming unresponsive
when the Parallel Redundancy Protocol (PRP) is enabled.
Clarified the message generated by the relay in response to an invalid
CID file.
Added local time and date analog quantities.
Improved relay performance during certain incorrect memory reads.