X35 ConsoleGeneral Operations
8.22
7. Turn the calibration valve OFF.
8. Weigh each sample and return to the cab to
enter weights.
a. Touch the right yellow arrow to move to
the next screen.
9. Enter the weights for each tank in the “Actual
W
eight column (Figure 8.41) and proceed to
the next step.
10. When calibrating for the first time it is
acceptable that calibration factor(s) might be
out +/- 20% depending on the product density
and other variations. You should save the
calibration factors and recalibrate any tanks
that are out more than 5%.
a. Refer to Figure 8.42. You can save
the
calibration factors for each tank
individually by selecting the button in the
Save column for desired tank, or you can
save calibration factors for all tanks at
once by selecting the save all button.
b. Recalibrate the tanks until within 5%, to
confirm your new calibration factor.
11. Close out of the calibration window.
12. Return to the Seeder Controller main viewing
area in preparation for seeding.
Figure 8.42 - Saving Calibration Factors
Use buttons in this column
to save calibration factors
for an individual tank
Save all new
calibration
factors
Restore all
calibration factors
to old value