Example 2: When using the counter instruction between JP and LBL
Timing chart 1
R0
X100
Final timing of
the previous
non-execution of
JP instruction
Count
operation
This is not counted because X0 as the trigger
(execution condition) for counter input has not
been changed after the final timing of the
previous non-execution of JP instruction.
Timing chart 2
R0
X100
This is counted because counter input has
been changed from OFF to ON after the final
timing of the previous non-execution of JP
instruction
Count
operation
Final timing of
the previous
non-execution of
JP instruction
19.7 Rise Detection Method
19-18 WUME-FP7CPUPGR-12