RFL 9300 RFL Electronics Inc.
August 9, 2001 4 - 14 (973) 334-3100
4.2.34 TRIP RLS – TRIP RELEASE
Parameter #145 (TRIP RLS) determines the method used by the Display Controller to release a
latched output trip signal. Three methods of trip release are available:
1. Output trip will unlatch when both the internal trip and DC trip current sense signals are
no longer active.
2. Output trip will be unlatched 100ms after the internal trip signal is no longer active.
3. Output trip will be released with 0ms delay when the internal trip signal becomes inac-
tive.
(Note that the internal trip signals are supplied by the Phase Controllers)