EasyManua.ls Logo

RFL Electronics RFL 9300 - Figure 8-6. Correctly Wired Two-Terminal System; Figure 8-7. Phase Inversion at Remote 1 Relay

RFL Electronics RFL 9300
553 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.4.4.5.1 Two Terminal Systems
If the terminals are wired correctly, then the current going into the local relay
will be the same as the current go-
ing out of the remote 1 relay
, and the differential current on Phase A will be zero. This can be seen in Figure 8-
6.
RFL 9300 RFL Electronics Inc.
October 20, 2004 8 - 31 (973) 334-3100
Station A
Station B
RFL 9300
Two
Terminal
RFL 9300
Two
Terminal
Communications Channel
Local Remote
2 Am
1
p
s
2 Amps
Figure 8-6. Correctly wired two-terminal system
If there is a phase inversion at the remote 1 relay, the resulting differential current indicated at both stations will
be approximately double the current, or about four amps. This can be seen in Figure 8-7.
Station A
Station B
2 Am
p
s
2 Amps
RFL 9300
Two
Terminal
RFL 9300
Two
Terminal
Communications Channel
Local Remote
Phase input to
remote 1 relay
inverted
1
Figure 8-7. Phase inversion at remote 1 relay

Table of Contents